Assessment Of Harmonics Distortionat Communication Company Supply

Assessment Of Harmonics Distortionat Communication Company Supply

Show simple item record

dc.contributor.advisor Sharif Fadul Babikir en_US
dc.contributor.author Ismail, Imad Eldin Abdalla
dc.contributor.other Electrical and Electronic Engineering en_US
dc.date 2015
dc.date.accessioned 2015-11-15T07:19:57Z
dc.date.available 2015-11-15T07:19:57Z
dc.date.issued 2015-11-15
dc.date.submitted 2015
dc.identifier.uri http://khartoumspace.uofk.edu/123456789/17073
dc.description 53 Pages
dc.description.abstract This thesis mainly assesses and analyses the harmonics measured at point of common coupling (PCC) at the secondary side of service transformer #1 of MTN Communication Company and compares it with international standards IEEE 519-1992. Fluke 435-II power quality analyzer has been used in the measurements procedure. The total current harmonics distortion was measured to be around 19.3%, whereas the total voltage harmonics distortion was measured to be within the acceptable standard level i.e. 5.1%. Filters are effectively used to remove most of the low frequency harmonics. Active filter is recommended to be designed to reduce the total current harmonics to acceptable standard level i.e. 5% instead of 19.3%. This thesis mainly assesses and analyses the harmonics measured at point of common coupling (PCC) at the secondary side of service transformer #1 of MTN Communication Company and compares it with international standards IEEE 519-1992. Fluke 435-II power quality analyzer has been used in the measurements procedure. The total current harmonics distortion was measured to be around 19.3%, whereas the total voltage harmonics distortion was measured to be within the acceptable standard level i.e. 5.1%. Filters are effectively used to remove most of the low frequency harmonics. Active filter is recommended to be designed to reduce the total current harmonics to acceptable standard level i.e. 5% instead of 19.3%. en_US
dc.publisher university of khartoum en_US
dc.subject Harmonics Distortiona ;Communication Company Supply;harmonics;Effects of harmonics distortion en_US
dc.title Assessment Of Harmonics Distortionat Communication Company Supply en_US
dc.type Thesis en_US
dc.Degree M.Sc en_US
dc.Faculty Engineering en_US
dc.description.arabic-abstract تناولت هذه الأطروحة بالتقييم والتحليل التوافقيات والتى تم قياسها بالنقطة المشتركة (PCC) عند المدخل الرئيس للخدمة ناحية الجهد المنخفض لمغذى محول الخدمة رقم (1) لشركة الإتصالات (MTN) و مقارنة ذلك بالمقاييس العالمية (IEEE 519-1992). تم إستخدام جهاز تحليل جودة القدرة الكهربائية من نوع (Fluke 435-II) في عملية القياس. هذا وقد تم قياس تيار التوافقيات الإجمالى (THD) ليكون فى حدود حوالى 19.3% ، بينما تم قياس جهد التوافقيات الإجمالى ليكون فى الحدود القياسية المسموح بها حوالى 5.1%. المرشحات (FILTERS)يتم إستخدامها بفعالية فى إزالة معظم التوافقيات ذات التردد المنخفض وقد أوصت الدراسة بتصميم مرشح لخفض تيار التوافقيات الإجمالى ليكون فى الحدود القياسية المسموح بها أى 5% عوضاً عن 19.3 % . en_US